The electronic temperature controller PTM-2000 is an eight-channel temperature monitoring and four-channel control device. PTM-2000 controller is used as a part of various electric heating cable systems and ensures optimal temperature maintenance for each channel. The algorithms used for heating control, in combination with a wide range of different sensor types, ensure optimum control of the heat tracing and saves energy.
The temperature control will be realized by using processing signals received from temperature, precipitation and water sensors. The PTM-2000 can be integrated into computerized process control systems via data transmission interface RS485 or MOD_BUS/RTU. The heating control is effected by means of output relay channels. All operating parameters and conditions of the connected heating systems are displayed with a display. The PTM-2000 controller is designed to be mounted on a DIN rail 35 mm in control cabinets.
System operation temperature |
−100 ... +600 °C with 4...20 mA −100 ... +600 °C with PT100 −55 ... +60 °C with TST01 standard −55 ... +125 °C with TST01 silicone |
---|---|
Supply voltage | 90...245 VAC, 50...60 Hz |
Power consumption | 12 W |
Dimensions (WxHxD) | 90×160×60 mm |
Weight | 450 g |
Operating temperature range | +5 ... +40 °C |
Relative humidity (at 30 °C) | 90 % |
Degree of protection | IP20 |
Mounting type | DIN-rail, 9 modules |
Interface, communication protocol | RS485, MOD_BUS/RTU |
Type of sensors (not included in delivery kit) |
TST01, TSP02, TSP03-D, TSW01, up to 4 pcs. PT100 sensors when using 24V thermal 4...20 mA signal converter(s) |
Maximum sensor distance from the controller |
1000 m for normalized signal
4...20 mA 100 m for temperature sensor TST01 |
Number of temperature measurement channels |
8 channels: - 4 sensors TST01 (DS18S20) - 4 signals 4...20 mA |
Number of precipitation and water measurement channels |
6 channels: - 2 precipitation sensors - 4 water sensors |
Number of control channels |
4 channels (K1...K4) for pipe or roof heating or 3 channels for roof plus one for open area or 2 channels for roof plus 2 channels for open area or 2 channels for area heating 6A / 230 VAC, 50...60 Hz |
Number of emergency channels | 1 channel (K5) 6A / 230 VAC, 50...60 Hz |
Number of indication channels | 1 channel (K0) 3A / 230 VAC, 50...60 Hz |
Color |
Light-grey face enclosure Black enclosure base |